Connecting Technology, Securing Tomorrow.

Access Controller

SKU : DS-K2704X(P)

Please Login to View Price

  • Supports 8-door control. It is formed by 2 DS-K2M002X access modules, and one 4-doors access controller
  • Access controller: downstream RS-485 redundancy wiring design to ensure communication stability. 5-ch downlink RS-485 interface supports two applications: 1. When 4-ch RS-485 communication, the 5th RS-485 can be used as a redundant application; 2. 4-ch RS-485 forms 2 groups of dual-bus loops with physical isolation. It is recommended that you do not have more than 16 access modules attached to each loop bus. Access Module: supports 8-ch RS-485 interface for card reader connecting
  • Web configuration management. All configurations can be realized via web without software application
  • Supports professional access control applications such as multi-door interlocking and anti-passback
  • Supports backup battery access. Charging and discharging are available
  • It has status indicators such as power supply, communication and operation, which is convenient for equipment health detection
System
  • Operating system : Linux
Network
  • Wired network : 1, 10/100/1000 Mbps self-adaptive
Interface
  • Network interface : 1
  • Lock control : 4
  • Exit button :4
  • Door contact input : 4
  • Alarm input : 8
  • Alarm output : 4
  • TAMPER : 1
  • RS-485 : 7, 2 for card reader, 5 for access modules (4 for communication, each interface can connect up to 16 access modules; 1 for redundancy)
  • Wiegand : 4, standard 26/34 input, supports custom Wiegand settings
  • USB : 1, USB 2.0
  • Fire interface : 1
Capacity
  • User capacity : 100,000
  • Fingerprint capacity : 10,000
  • Card capacity : 200,000
  • Event capacity : 600,000
  • Linked door capacity :

    Self: 4 doors

    Extended: up to 128 doors (connected with 62 access modules)

  • Linked card reader capaciry : 8 RS-485 card readers (OSDP protocol) and 4 Wiegand card readers
Authentication
  • Fingerprint recognition duration : < 1 s
General
  • Indicator : 12 indicators, 1 for indicating power status, 1 for running status, 1 for wired network status, 5 for RS-485 status, and 4 for door status
  • Battery : Charge and discharge
  • Power supply : 100 VAC to 240 VAC, standard PoE
  • Power consumption : ≤ 102 W
  • Working temperature : -10 °C to 55 °C (14 °F to 131 ° F)
  • Working humidity : 0% to 90% (No condensing)
  • Installation : Installation with guide rail
  • Language : English, Thai, Traditional Chinese, Indonesian, Vietnamese, Arabic, Spanish (Europe), Spanish (South America), Italian, French, Dutch, Russian, Ukrainian, Portuguese (Europe), Portuguese (Brazil), Serbian, Croatian, Bulgarian, German, Greek, Romanian
Function
  • Configuration via Web browser : Support
  • Multi-factor authentication : Support
  • First person in : Support
  • Anti-passback : Support 32 routes (64 card readers each)
  • Multi-door interlocking : Support 32 groups (32 doors each)